Adds the 2026-11-01 bench record, on main at a251158, gen2 Nano.

Of the cut-short replies, 13 of 187 in C0 passed the CRC as an all-0xFF payload, against the 1 in 256 that feastorg/CRUMBS#130 assumes.

Records #76, #77 and #83 on the gen2 Nano at a251158: all pass, and
F4's over-temperature latch shows amber. Adds the #81 bisect: removing
only main.cpp's masked windows, or slowing the loop, takes cut-short
GET_STATE replies from 187 in 300 s to 0. Includes the bisect patch.
@CameronBrooks11
CameronBrooks11 merged commit 393b74f into main Nov 1, 2026
11 checks passed
@CameronBrooks11
CameronBrooks11 deleted the docs/bench-2026-11-01 branch November 1, 2026 18:45
CameronBrooks11 added a commit that referenced this pull request Nov 2, 2026
Fixes #81, the GET_STATE replies cut short on the gen2 Nano.

The 2026-11-01 bisect (#84) traced the cut-short replies to how often
the loop masks interrupts. With `main.cpp`'s masked windows removed, or
with the loop slowed by 300 us a pass, the bad-reply rate went from 187
in 300 s to 0. `relayControlLogic()` opened four masked windows on every
pass: three snapshots and the on-time commit.

What changes:

- `relayControlLogic()` takes its snapshot, runs the PIDs and publishes
the on-times only on a new thermocouple reading, or once
`RLHT_SNAPSHOT_INTERVAL_MS` (default 10, a `-D` override) has passed. In
between, `actuateRelay()` drives from the last snapshot.
- The PIDs still compute once per reading (#76), since a reading always
triggers a snapshot.
- The e-stop, watchdog-trip and fault hold is checked on every pass with
no masked window. Each flag is one byte and only the main loop sets
them. The relay state fields are written only when they change.
- A command now waits up to the interval to reach a relay: 10 ms, next
to a 1000 ms relay period.
- An invalid mode now holds both relays off through drives of 0, where
before it returned early from each pass.

I rejected a per-command "changed" flag set by every handler: a handler
that missed setting it would leave a stale setpoint or mode. A fixed
interval can't miss anything.

## Test

`test_mask_rate` counts `noInterrupts()` calls through the host stub
over 3 s of closed-loop heating:

| | Passes that opened a masked window |
| --- | --- |
| main's `relayControlLogic()` | 1500 of 1500: the check fails |
| this branch | 302 of 1500, against an allowance of 312 (one per 10 ms
plus one per reading) |

It also checks that a duty change reaches relay 1 within the interval
(10 ms) and that the e-stop drops relay 1 on the next pass.

`make -C test/host`: 732 ok, 0 failed, across the four envs. That's
main's 696 plus `test_mask_rate`'s 36.

`pio run`, 0 warnings:

| env | Flash | RAM | Flash vs main |
| --- | --- | --- | --- |
| `gen1_nano` | 23018 B | 918 B | |
| `gen2_nano` | 24246 B | 934 B | +208 B, +12 B RAM |
| `gen1_nanoevery` | 24505 B | 996 B | |
| `gen2_nanoevery` | 25717 B | 1014 B | |

## Bench

gen2 Nano on the backplane, Pi 4 at 50 kHz, `replylog.py 19 1 300` with
retries off:

| Build | Bad replies in 300 s |
| --- | --- |
| main `a251158` (2026-11-01, two captures) | 187 / 2552 and 175 / 2552
|
| this branch (2026-11-02) | 1 / 2551 |

The one bad frame went to 0xFF at the CRC byte and was caught. That's
the rate Slice_DCMT's gen2 Nano showed on the same bus on 2026-10-31 (1
/ 2555).

Not run on the board: the heaters under closed-loop control on this
build. The host tests cover the control paths.