5 changes: 5 additions & 0 deletions .changeset/deadband-exit-withdraws-blocked-charge.md
Original file line number Diff line number Diff line change
@@ -0,0 +1,5 @@
---
"ftw": patch
---

A battery can no longer keep charging against a charge block that the site has already closed. The reactive control arm stops early when grid power is close enough to its target, and it issued no command when it did — but a battery holds its last setpoint until it gets another one, so an earlier charge command kept running. The trap is that the charge itself is what keeps the meter near target: on a planner slot that forbids charging, a battery absorbing a 2 kW solar surplus holds the meter at −50 W, the error stays inside the deadband, and the tick that would have stopped the charge walks away for as long as the sun holds. The surplus the slot exists to export goes into the pack instead. The same silence kept a battery charging after its own driver reported that it cannot charge. Such a tick now commands zero, and a deadband tick with nothing blocked still commands nothing.
325 changes: 325 additions & 0 deletions go/internal/control/deadband_charge_block_test.go
Original file line number Diff line number Diff line change
@@ -0,0 +1,325 @@
package control

// What an early exit owes a battery whose charge direction is closed.
//
// floorBlockedCharge (#809) runs inside applyDispatchSafetyPipeline. The
// three early exits — idle, holdoff, reactive deadband — return through
// fuseSaverEarlyExit and never reach it. An exit that issues no target
// withdraws nothing: main.go only sends commands for the targets
// ComputeDispatch returned, and a driver holds its last accepted setpoint
// until it gets another one.
//
// Only the deadband exit turns that into a trap that does not end, because
// its own condition can be satisfied BY the violation: the battery absorbing
// the surplus is what keeps the meter near target. The tests below split into
// three groups — the deadband cases the fix withdraws, the quiet ticks it
// must leave quiet, and the two exits deliberately left alone with the
// evidence for why.

import (
"encoding/json"
"math"
"testing"
"time"

"github.com/srcfl/ftw/go/internal/telemetry"
)

type deadbandBattery struct {
name string
currentW, soc float64
capability string
}

func seedDeadbandSite(gridW float64, bats []deadbandBattery) *telemetry.Store {
s := telemetry.NewStore()
s.Update("meter", telemetry.DerMeter, gridW, nil, nil)
s.DriverHealthMut("meter").RecordSuccess()
for _, b := range bats {
soc := b.soc
var data json.RawMessage
if b.capability != "" {
data = json.RawMessage(b.capability)
}
s.Update(b.name, telemetry.DerBattery, b.currentW, &soc, data)
s.DriverHealthMut(b.name).RecordSuccess()
}
return s
}

// passiveArbitrageIdleState builds a site on a passive-arbitrage idle slot —
// the slot whose live-export gate closes the charge direction site-wide.
func passiveArbitrageIdleState(now time.Time) *State {
st := NewState(0, 60, "meter")
st.Mode = ModePlannerPassiveArbitrage
st.UseEnergyDispatch = true
st.SlewRateW = 500
st.MinDispatchIntervalS = 0
st.SlotDirective = func(time.Time) (SlotDirective, bool) {
return SlotDirective{
SlotStart: now.Add(-7 * time.Minute),
SlotEnd: now.Add(8 * time.Minute),
BatteryEnergyWh: 0,
Strategy: "passive_arbitrage",
}, true
}
return st
}

// ---- The deadband cases the fix withdraws ----

// The reproduction, from the P2 raised on #809. An idle arbitrage slot over a
// 2 kW PV surplus: the battery eats the surplus, so the meter reads -50 W and
// the grid error sits inside the 60 W deadband. The tick that would have
// stopped the charge walks away because the charge is what makes the error
// small — the violation sustains the condition that hides it, tick after
// tick, for as long as the sun holds. Nothing downstream withdraws the
// earlier charge command, so the surplus the slot exists to export goes into
// the pack instead.
func TestDeadbandExitMayNotStrandBlockedCharge(t *testing.T) {
now := time.Now()
store := seedDeadbandSite(-50, []deadbandBattery{{"ferroamp", 2000, 0.55, ""}})
st := passiveArbitrageIdleState(now)

targets := ComputeDispatch(store, st, caps(map[string]float64{"ferroamp": 15200}), 11040)
if len(targets) == 0 {
t.Fatalf("no target issued — the tick left the battery charging at +2000 W into a closed charge direction")
}
got := targetsByDriver(targets)
if math.Abs(got["ferroamp"].TargetW) > 0.01 {
t.Errorf("ferroamp TargetW = %.1f W, want 0 W — an idle arbitrage slot over an exporting baseline forbids charge",
got["ferroamp"].TargetW)
}
}

// Same law through the second site-wide authority: planner_self with no fresh
// plan is discharge-only. The battery is charging at +2500 W and the meter is
// 40 W inside the deadband because of it.
func TestDeadbandExitMayNotStrandStalePlanChargeBlock(t *testing.T) {
store := seedDeadbandSite(-40, []deadbandBattery{{"ferroamp", 2500, 0.60, ""}})
st := NewState(0, 60, "meter")
st.Mode = ModePlannerSelf
st.UseEnergyDispatch = true
st.SlewRateW = 500
st.MinDispatchIntervalS = 0
st.SlotDirective = func(time.Time) (SlotDirective, bool) { return SlotDirective{}, false }
st.PlanTarget = func(time.Time) (string, float64, bool) { return "", 0, false }

targets := ComputeDispatch(store, st, caps(map[string]float64{"ferroamp": 15200}), 11040)
if len(targets) == 0 {
t.Fatalf("no target issued — a stale plan left the battery charging at +2500 W")
}
got := targetsByDriver(targets)
if math.Abs(got["ferroamp"].TargetW) > 0.01 {
t.Errorf("ferroamp TargetW = %.1f W, want 0 W — planner_self on a stale plan may not charge",
got["ferroamp"].TargetW)
}
if !st.PlanStale {
t.Errorf("scenario did not arm the stale-plan gate — the test proves nothing")
}
}

// The per-driver authority: the driver itself reported charge_capable=false
// while measured mid-charge. Same deadband, same silence, and the earlier
// charge command keeps running into hardware that has said it cannot take it.
func TestDeadbandExitMayNotStrandChargeBlockedDriver(t *testing.T) {
store := seedDeadbandSite(-30, []deadbandBattery{
{"ferroamp", 2000, 0.50, `{"discharge_capable":true,"charge_capable":false}`},
})
st := NewState(0, 60, "meter")
st.Mode = ModeSelfConsumption
st.SlewRateW = 500
st.MinDispatchIntervalS = 0

targets := ComputeDispatch(store, st, caps(map[string]float64{"ferroamp": 15200}), 11040)
if len(targets) == 0 {
t.Fatalf("no target issued — the driver said it cannot charge and was left charging at +2000 W")
}
got := targetsByDriver(targets)
if math.Abs(got["ferroamp"].TargetW) > 0.01 {
t.Errorf("ferroamp TargetW = %.1f W, want 0 W — the driver reported charge_capable=false",
got["ferroamp"].TargetW)
}
}

// ---- The quiet ticks the fix must leave quiet ----

// The guard that bounds the whole change: a deadband tick with nothing
// blocked issues nothing, exactly as before. A battery measured charging is
// not by itself a reason to speak — most of a sunny day looks like this, and
// turning those ticks into commands would put a driver refusal counter (#800)
// behind every one of them.
func TestDeadbandExitStaysQuietWhenNothingIsBlocked(t *testing.T) {
store := seedDeadbandSite(-30, []deadbandBattery{{"ferroamp", 2000, 0.50, ""}})
st := NewState(0, 60, "meter")
st.Mode = ModeSelfConsumption
st.SlewRateW = 500
st.MinDispatchIntervalS = 0

targets := ComputeDispatch(store, st, caps(map[string]float64{"ferroamp": 15200}), 11040)
if len(targets) != 0 {
t.Errorf("deadband tick issued %d target(s) %v — no gate closed charge here, the tick must stay quiet",
len(targets), targets)
}
}

// The other half of the guard: the block is armed, but no battery is charging
// against it, so there is nothing to withdraw and the tick stays quiet. This
// is what keeps the predicate "a blocked battery is charging" rather than the
// much broader "a block exists" — the latter would speak on every deadband
// tick of an idle arbitrage slot, all night.
func TestDeadbandExitStaysQuietWhenTheBlockedBatteryIsIdle(t *testing.T) {
now := time.Now()
store := seedDeadbandSite(-30, []deadbandBattery{{"ferroamp", 0, 0.55, ""}})
st := passiveArbitrageIdleState(now)

targets := ComputeDispatch(store, st, caps(map[string]float64{"ferroamp": 15200}), 11040)
if len(targets) != 0 {
t.Errorf("deadband tick issued %d target(s) %v — the charge block had nothing to withdraw",
len(targets), targets)
}
}

// A blocked battery measured DISCHARGING is not charging against its block
// either. The charge floor is one-sided and so is the exit that feeds it.
func TestDeadbandExitStaysQuietWhenTheBlockedBatteryIsDischarging(t *testing.T) {
now := time.Now()
store := seedDeadbandSite(30, []deadbandBattery{{"ferroamp", -2000, 0.55, ""}})
st := passiveArbitrageIdleState(now)

targets := ComputeDispatch(store, st, caps(map[string]float64{"ferroamp": 15200}), 11040)
if len(targets) != 0 {
t.Errorf("deadband tick issued %d target(s) %v — a discharging battery is not charging against a charge block",
len(targets), targets)
}
}

// The discharge-side clause on the line above the new one still behaves the
// same way. It was the precedent for this fix; a regression in it would make
// the argument for the fix false.
func TestDeadbandDischargeCarveOutStillFires(t *testing.T) {
now := time.Now()
store := seedDeadbandSite(30, []deadbandBattery{{"ferroamp", -2000, 0.55, ""}})
st := NewState(0, 60, "meter")
st.Mode = ModePlannerCheap
st.UseEnergyDispatch = true
st.SlewRateW = 500
st.MinDispatchIntervalS = 0
st.SlotDirective = func(time.Time) (SlotDirective, bool) { return SlotDirective{}, false }
st.PlanTarget = func(time.Time) (string, float64, bool) { return "charge", 0, true }
_ = now

targets := ComputeDispatch(store, st, caps(map[string]float64{"ferroamp": 15200}), 11040)
if len(targets) == 0 {
t.Fatalf("no target issued — a charge slot with the battery discharging must not take the deadband exit")
}
}

// ---- The two exits left alone, and the evidence ----

// The holdoff exit reaches no charge block either, and does not need to. It
// only arms after a dispatch actually happened, and fuseSaverEarlyExit
// refreshes LastDispatch only when the fuse-saver fires, so the window is
// bounded by MinDispatchIntervalS and then the normal path runs. This test
// pins that bound: identical inputs, quiet inside the window, withdrawn the
// moment it expires. Reaching the block from the holdoff exit would mean
// hoisting the meter read, the battery gather and the gate computation above
// it — and the two planner_self gates that ARE known there without the
// arbitrage one are exactly the partial enumeration #809 argued against.
func TestHoldoffDelaysTheChargeBlockButDoesNotDefeatIt(t *testing.T) {
now := time.Now()
caps := caps(map[string]float64{"ferroamp": 15200})

inWindow := passiveArbitrageIdleState(now)
inWindow.MinDispatchIntervalS = 5
recent := now.Add(-1 * time.Second)
inWindow.LastDispatch = &recent
held := ComputeDispatch(seedDeadbandSite(-50, []deadbandBattery{{"ferroamp", 2000, 0.55, ""}}), inWindow, caps, 11040)
if len(held) != 0 {
t.Errorf("holdoff tick issued %d target(s) %v — the holdoff window suppresses re-dispatch", len(held), held)
}

expired := passiveArbitrageIdleState(now)
expired.MinDispatchIntervalS = 5
stale := now.Add(-30 * time.Second)
expired.LastDispatch = &stale
after := ComputeDispatch(seedDeadbandSite(-50, []deadbandBattery{{"ferroamp", 2000, 0.55, ""}}), expired, caps, 11040)
if len(after) == 0 {
t.Fatalf("holdoff expired and the charge block still issued nothing — the delay became a defeat")
}
if got := targetsByDriver(after); math.Abs(got["ferroamp"].TargetW) > 0.01 {
t.Errorf("ferroamp TargetW = %.1f W, want 0 W once the holdoff window has passed", got["ferroamp"].TargetW)
}
}

// The idle exit is left alone because it withholds commands from every
// battery equally — that is idle's declared contract ("Do nothing — no
// dispatch", modes_catalog.go). It is not a charge-block bypass: the
// site-wide block cannot be armed there at all, because effectiveMode reaches
// ModeIdle only from the operator's own idle mode or from a planner slot that
// took the branch where all three noSelfCharge gates are false. What remains
// is the per-driver report, and this test pins that idle treats it exactly as
// it treats an unblocked battery. If somebody later decides idle must
// withdraw the previous command on entry, this test moves — and it should,
// because that is a decision about what idle means, not about charge blocks.
func TestIdleExitWithholdsCommandsFromBlockedAndUnblockedAlike(t *testing.T) {
caps := caps(map[string]float64{"ferroamp": 15200})

blocked := NewState(0, 60, "meter")
blocked.Mode = ModeIdle
blocked.MinDispatchIntervalS = 0
blockedOut := ComputeDispatch(
seedDeadbandSite(-2000, []deadbandBattery{
{"ferroamp", 2000, 0.50, `{"discharge_capable":true,"charge_capable":false}`},
}), blocked, caps, 11040)

unblocked := NewState(0, 60, "meter")
unblocked.Mode = ModeIdle
unblocked.MinDispatchIntervalS = 0
unblockedOut := ComputeDispatch(
seedDeadbandSite(-2000, []deadbandBattery{{"ferroamp", 2000, 0.50, ""}}),
unblocked, caps, 11040)

if len(blockedOut) != len(unblockedOut) {
t.Errorf("idle treated a charge-blocked battery differently: blocked=%v unblocked=%v", blockedOut, unblockedOut)
}
if len(blockedOut) != 0 {
t.Errorf("idle issued %d target(s) %v — idle mode dispatches nothing", len(blockedOut), blockedOut)
}
}

// The predicate's contract, pinned directly so the deadband condition cannot
// drift away from floorBlockedCharge's two authorities.
func TestAnyBlockedBatteryChargingContract(t *testing.T) {
charging := []batteryInfo{{driver: "a", currentW: 2000}}
idle := []batteryInfo{{driver: "a", currentW: 0}}
discharging := []batteryInfo{{driver: "a", currentW: -2000}}
chargingBlocked := []batteryInfo{{driver: "a", currentW: 2000, chargeBlocked: true}}
mixed := []batteryInfo{
{driver: "a", currentW: -2000, chargeBlocked: true},
{driver: "b", currentW: 2000},
}

cases := []struct {
name string
bats []batteryInfo
noSelfCharge bool
want bool
}{
{"site-wide block, charging", charging, true, true},
{"site-wide block, idle", idle, true, false},
{"site-wide block, discharging", discharging, true, false},
{"no block, charging", charging, false, false},
{"per-driver block, charging", chargingBlocked, false, true},
{"per-driver block, only the unblocked one charges", mixed, false, false},
{"site-wide block reaches the unblocked one", mixed, true, true},
{"nothing at all", nil, false, false},
}
for _, c := range cases {
t.Run(c.name, func(t *testing.T) {
if got := anyBlockedBatteryCharging(c.bats, c.noSelfCharge); got != c.want {
t.Errorf("anyBlockedBatteryCharging = %v, want %v", got, c.want)
}
})
}
}
49 changes: 48 additions & 1 deletion go/internal/control/dispatch.go
Original file line number Diff line number Diff line change
Expand Up @@ -1829,9 +1829,25 @@ func ComputeDispatch(
// stuck at that previous level, defeating the whole point of
// the reserve. Falling through forces a fresh dispatch that
// drives the battery toward 0 (or the post-PI cap below).
//
// The charge-side clause is the mirror of the discharge one on
// the line above it, and it is here for the same reason: a
// small grid error can be small BECAUSE the battery is doing
// the forbidden thing. An idle arbitrage slot over a 2 kW PV
// surplus reads -50 W at the meter while the battery absorbs
// the other 2000 W; the error stays inside the deadband for as
// long as the violation lasts, and no tick ever reaches
// floorBlockedCharge to stop it. Falling through issues the 0 W
// the block already decided. Gated on a battery MEASURED
// charging, not on the block alone, so a tick with nothing to
// withdraw stays quiet and no driver is handed a command it
// could refuse. Safety does not thin out on this path: the
// full pipeline ends in the same forceFuseDischarge the
// early exit's fuse-saver would have run.
surplusActive := state.EVSurplusOnlyReserveW > 0 && effectiveMode == ModeSelfConsumption
if !surplusActive && math.Abs(errW) < state.GridToleranceW &&
!(noSelfDischarge && anyBatteryDischarging(onlineBats)) {
!(noSelfDischarge && anyBatteryDischarging(onlineBats)) &&
!anyBlockedBatteryCharging(onlineBats, noSelfCharge) {
// A small grid error is not a statement that the site is
// safe. errW compares one aggregate number against one
// aggregate target; two protections bind on numbers this
Expand Down Expand Up @@ -3026,6 +3042,37 @@ func anyBatteryDischarging(bats []batteryInfo) bool {
return false
}

// anyBlockedBatteryCharging reports whether a battery whose charge direction
// this tick has closed is measured charging right now. It is the charge-side
// twin of anyBatteryDischarging, and it exists for the deadband exit: an
// exit that issues no target withdraws nothing, because the control tick
// only sends commands for targets ComputeDispatch returned and a driver
// holds its last accepted setpoint until it gets another one.
//
// Both authorities that floorBlockedCharge honours are read here, so the two
// cannot drift apart:
//
// - noSelfCharge — the site-wide block, already computed above.
// - chargeBlocked — the driver's own capability report.
//
// MEASURED charge, not the previous command, decides. That mirrors
// anyBatteryDischarging's ±1 W test and keeps the predicate honest: a
// battery that is not actually charging has nothing to withdraw, so the
// tick stays quiet and no driver is handed a command it could refuse. The
// cost is that a fresh charge command not yet visible at the meter waits one
// tick, which is the same latency the discharge side has always accepted.
func anyBlockedBatteryCharging(bats []batteryInfo, noSelfCharge bool) bool {
for _, b := range bats {
if b.currentW <= 1 {
continue
}
if noSelfCharge || b.chargeBlocked {
return true
}
}
return false
}

type surplusAccounting struct {
rawGridW float64
effectiveGridW float64
Expand Down